Earth tester is used
for measurement of Earth resistance. If
earth resistance is more, proper treatment is to be given. For measurement of
earth pit resistance, pit earthing connection should be disconnected from main
grid. Thereafter, measurement is to be carried out by three point method.
Working of Earth Tester: - There is hand operated D.C. Generator. While feeding current to spike, D.C. current is converted into A.C. current by the converter and A.C. current received from spike is again converted in D.C. current by the help of rectifier, while going to generator. A.C. current is fed to the spike driven in earth because there should not be electrolytic effect.
Measurement of Earth Resistance (Three point method):-
In this method, earth tester terminals C1 & P1 are shorted to each other and connected to the earth electrode (pipe) under test. Terminals P2 & C2 are connected to the two separate spikes driven in earth. These two spikes are kept in same line at the distance of 25 meters and 50 meters due to which there will not be mutual interference in the field of individual spikes. If we rotate generator handle with specific speed we get directly earth resistance on scale.
Acceptable Limit: Value of earth pit resistance should be less than or equal to 1Ω with grid and without grid 10 Ω