Neutral Earthing Transformer Size Calculation


Neutral Earthing Transformer Size Calculation

A Neutral Earthing Transformer (NET), also known as a Neutral Grounding Transformer, is used to provide a neutral point for grounding in systems that don't have a natural neutral connection, such as delta-connected transformer systems. It helps in maintaining system stability, protecting equipment, and improving safety during fault conditions like ground faults. Determining the appropriate size of a Neutral Earthing Transformer is critical for system performance and safety.

Purpose of a Neutral Earthing Transformer

  1. Ground Fault Protection: It limits fault currents during a ground fault, preventing damage to the equipment and maintaining system stability.
  2. Creating an Artificial Neutral Point: In systems like delta-connected transformers or ungrounded systems, a NET provides a neutral point for grounding.
  3. Controlled Earthing: It allows the earthing of the neutral point through a resistor or reactor, controlling the magnitude of ground fault currents.

Factors to Consider in NET Sizing

When determining the appropriate size of a Neutral Earthing Transformer, several factors must be taken into account:

  1. System Voltage (Line-to-Line Voltage): The system’s voltage level directly affects the design of the NET, as it defines the insulation level and the turn ratios of the transformer.
  2. Fault Current Level: The NET should be sized based on the expected ground fault current levels. A high ground fault current may require a larger transformer.
  3. Duration of Fault Current: The duration for which the NET must withstand the fault current influences the thermal capacity of the transformer. Generally, fault durations are between 1 to 10 seconds.
  4. Earthing Resistor Value: If an earthing resistor is used, its value impacts the magnitude of the current flowing through the NET during a fault.

Steps for Calculating the Size of a Neutral Earthing Transformer

The process of calculating the size of a Neutral Earthing Transformer involves determining its rating (in kVA), impedance, and other characteristics to match the fault conditions of the system. Here are the steps:

1. Calculate the Fault Current (If)

The fault current that the NET should handle is typically defined by the earthing resistor value and system voltage. The formula for calculating the fault current through the NET is:

If=VLNReI_f = \frac{V_{LN}}{R_e}

Where:

  • If = fault current (A)
  • VLN = line-to-neutral voltage of the system (V)
  • Re = earthing resistor value (Ω)

2. Calculate the kVA Rating of the NET

This formula helps determine the capacity of the NET to handle the specified fault current for a given system voltage.

3. Duration of Fault Current

The duration for which the NET must withstand the fault current is also a crucial consideration. The thermal capacity of the NET is designed to withstand the specified fault current for a given time period (usually 1 to 10 seconds). The thermal capacity rating must match this duration to ensure that the transformer can safely handle the fault without overheating.

4. Continuous Rating (for Continuous Neutral Load)

If the NET is expected to carry a continuous neutral load (not just during faults), then its continuous rating should be considered. This continuous rating is typically lower than the short-time fault current rating but is important for systems with neutral loads.

Example Calculation

Assume a 6.6 kV (line-to-line) system with an earthing resistor of 10 ohms, and the NET should handle a ground fault for 10 seconds.

Additional Considerations

  1. Over-Design for Safety: It is common practice to add a margin to the calculated kVA rating to account for possible fluctuations in system parameters.
  2. Type of NET: NETs can be zigzag or star-connected transformers. Zigzag transformers are often preferred for their better zero-sequence impedance and better fault-current control.
  3. Cooling Requirements: The NET may require specific cooling methods (like air or oil) depending on the fault current and duration.

Conclusion

The correct sizing of a Neutral Earthing Transformer is crucial for maintaining system stability and safety during ground faults. It involves determining the appropriate kVA rating based on system voltage, fault current, and fault duration. Proper calculation ensures that the NET can safely and effectively limit ground fault currents, providing reliable protection to the electrical network.

Click here (Download)

 Neutral Earthing Transformer Size Calculation 

Real-Time Application of Neutral Earthing Transformer (NET)

A Neutral Earthing Transformer (NET), also known as a Neutral Grounding Transformer (NGT), is used in power systems to provide a neutral point for earthing, typically for generators or transformers that operate without a physical neutral point. This type of transformer plays a critical role in improving the safety, reliability, and performance of electrical systems, particularly in industrial and utility applications.

What is a Neutral Earthing Transformer?

A Neutral Earthing Transformer is a special-purpose transformer that provides a neutral point to the system, allowing for the grounding of otherwise ungrounded or delta-connected systems. It creates a low impedance path for fault currents, particularly ground faults, and is often paired with a resistor or reactor to control the fault current.

The typical configurations of NETs include:

  • Zigzag Transformer: Commonly used to derive a neutral point without a physical center tap.
  • Wye-Delta Transformer: Used in some applications for creating a neutral from a delta-connected system.

Real-Time Applications of Neutral Earthing Transformers

  1. Ground Fault Protection in Power Generation:

    • In power plants, particularly those with generators connected in delta configurations, there is often no natural neutral point for grounding. A Neutral Earthing Transformer creates an artificial neutral point, which can then be grounded using a resistor.
    • This setup allows for controlled ground fault currents, providing protection to the generator windings and associated equipment from damage due to ground faults. It helps to prevent severe voltage imbalances during fault conditions.
  2. Enhancing Stability in Industrial Distribution Systems:

    • In industrial plants with multiple transformers or generator sets, the use of Neutral Earthing Transformers allows for proper system grounding, enhancing the stability and safety of the electrical system.
    • It helps in detecting ground faults more accurately and prevents transient overvoltages, which can damage sensitive equipment such as motors, drives, and control systems. This is crucial in environments like chemical plants, mining operations, and manufacturing facilities where continuous operations are essential.
  3. Fault Current Limitation in Medium Voltage Networks:

    • In medium voltage (MV) networks (e.g., 6.6 kV, 11 kV systems), Neutral Earthing Transformers are often used with grounding resistors to limit the fault current during single line-to-ground faults. This controlled fault current prevents equipment damage, reduces thermal and mechanical stresses, and minimizes disruptions to the network.
    • By limiting the fault current, it also allows for safe operation and maintenance of the power system, helping to ensure that protective relays and circuit breakers operate within their ratings.
  4. Stabilizing Power Systems in Renewable Energy:

    • In renewable energy systems such as wind farms or solar power plants, Neutral Earthing Transformers are used to provide an earthing reference for the inverters or the step-up transformers. This is particularly important when multiple inverter systems or transformers are connected in delta, which lack a natural grounding point.
    • By providing a stable ground reference, NETs help to maintain system voltage stability during ground faults and ensure safe disconnection of faulty equipment, improving the overall reliability of the renewable energy plant.
  5. Neutral Earthing in Substations:

    • Neutral Earthing Transformers are used in substations to ground the neutral of transformers that are delta connected. This enables better control and detection of ground faults on the primary side of a transformer.
    • It helps prevent overvoltages on healthy phases during ground faults and allows for the continued operation of the substation while the fault is being detected and isolated.

Key Benefits of Using Neutral Earthing Transformers

  1. Enhanced Fault Detection: NETs enable faster and more accurate detection of ground faults, which is critical in maintaining the safety and stability of power systems.
  2. Controlled Ground Fault Currents: By limiting the fault current through a connected resistor or reactor, NETs prevent damage to equipment and minimize disruptions in the event of a fault.
  3. Voltage Stability: Providing a stable ground reference helps to maintain balanced system voltages, even during asymmetrical faults, ensuring that sensitive equipment operates within safe limits.
  4. Protection of Equipment: The controlled grounding provided by a NET protects generators, transformers, and other equipment from severe overvoltages and thermal damage that can occur during faults.

Conclusion

Neutral Earthing Transformers are essential components in modern power systems, especially where ungrounded or delta-connected configurations are present. Their ability to provide a stable ground reference and control fault currents makes them invaluable in applications like power generation, industrial facilities, renewable energy systems, and medium-voltage networks. By ensuring safe grounding, they enhance the reliability and longevity of the electrical infrastructure, making them a critical element in achieving safe and efficient power distribution.

Neutral Earthing Transformer (NET) for a 1600 kVA, 11kV/415V System

A Neutral Earthing Transformer (NET) is used in power distribution systems to provide a neutral point for earthing, especially when the primary transformer is connected in a delta configuration (which lacks a neutral). The NET enables proper grounding and helps to limit the fault currents during earth faults, improving the safety and stability of the system.

For a 1600 kVA, 11kV/415V transformer, determining the NET parameters involves calculations related to earthing current, impedance, and the rating of the earthing transformer itself. Here’s a breakdown of the process:

Understanding the System Parameters

  • Transformer Rating: 1600 kVA
  • Primary Voltage: 11 kV (high voltage side)
  • Secondary Voltage: 415 V (low voltage side)
  • System Configuration: Typically, an 11kV/415V transformer has a delta-wye (Δ-Y) configuration, where the 11kV side is delta-connected and the 415V side is wye-connected with a neutral point.

Purpose of the Neutral Earthing Transformer (NET)

  • To provide a stable neutral point in an ungrounded or delta system.
  • To limit earth fault currents to safer levels, protecting equipment and personnel.
  • To facilitate the operation of protective relays during an earth fault condition.

Key Calculations for the NET

  1. Determine the Earthing Current: The earthing current depends on the fault level and the desired neutral current limit. Generally, the fault current limit is decided based on the protection settings and sensitivity of the relays.

    • For example, a common choice is to limit the fault current to 10A to 300A depending on the system design. This current value is chosen to allow enough current for proper relay operation while not damaging equipment.
  2. Selecting the Rating of the Neutral Earthing Transformer: The rating of the NET is based on the following formula:

    SNET=3×Vn×InS_{\text{NET}} = \sqrt{3} \times V_{\text{n}} \times I_{\text{n}}

Summary of NET Parameters for a 1600 kVA, 11kV/415V Transformer

  • NET Rating: Approximately 1.1 MVA for a fault current limit of 100A.
  • Impedance: Around 63.5 Ω for a 100A fault current at 6.35 kV.
  • Duration: Typically rated for 1 second or 10 seconds based on system protection needs.

Importance of Accurate NET Design

A properly designed NET is crucial for system safety, as it limits the earth fault current, which protects the transformer, downstream equipment, and personnel from potential damage due to overcurrent. Additionally, it ensures the proper operation of protective relays and avoids unnecessary tripping of breakers during earth faults.

By considering these calculations and selecting the appropriate NET parameters, the system can achieve a balance between safety, reliability, and cost-effectiveness.