Transformer Overcurrent and Earth fault Relay setting Calculation Excel


Transformer IDMT Over Current & Earth Fault Relay Setting

The Inverse Definite Minimum Time (IDMT) Overcurrent and Earth Fault relays are protection devices used in power systems to safeguard transformers, lines, and other electrical equipment from overcurrent and earth faults. These relays operate with a time delay, which varies inversely with the fault current magnitude, ensuring selective and coordinated protection.

1. IDMT Overcurrent Relay

The overcurrent relay is designed to protect the transformer from faults caused by excessive current, which may occur due to short circuits or overloading. The relay operates when the current flowing through the transformer exceeds a set threshold, known as the pickup current.

Key Settings for Overcurrent Relay:

  • Pickup Current (I> or I>>): This is the minimum current level at which the relay starts operating. The pickup setting is typically set between 110% - 150% of the rated transformer current. The value depends on the transformer’s rated current and the expected fault levels.

  • Time Multiplier Setting (TMS): The TMS adjusts the operating time of the relay once the current exceeds the pickup value. A lower TMS results in a faster relay operation for the same overcurrent value. The TMS is set based on the system’s protection coordination requirements.

  • Characteristic Curve: The relay's operating time is based on a predefined curve, typically following one of the following standards:

    • Standard inverse
    • Very inverse
    • Extremely inverse The inverse time characteristic ensures that the relay operates faster for higher fault currents but delays tripping for smaller overcurrent conditions, which might be tolerable for short periods.

2. IDMT Earth Fault Relay

The earth fault relay protects the transformer from earth or ground faults, which occur when there is an unintended connection between a phase conductor and the earth. These faults can result in severe damage due to large fault currents, which often have lower magnitude compared to phase faults but still pose serious risks.

Key Settings for Earth Fault Relay:

  • Pickup Current (I₀ or I>>>): The pickup current for the earth fault relay is typically set lower than that of the overcurrent relay. It usually ranges from 10% to 40% of the rated current depending on the system grounding and fault current levels.

  • Time Multiplier Setting (TMS): Similar to the overcurrent relay, the TMS for the earth fault relay controls the operating time. A proper setting ensures that the relay operates fast enough to clear faults while coordinating with other protective devices.

  • Characteristic Curve: The same type of inverse time curves is used as for the overcurrent relay, but with a different range to accommodate the nature of earth faults.

3. Relay Coordination

For optimal performance, relay coordination is crucial. Coordination ensures that only the closest protective device to the fault operates, while others remain in service. The overcurrent and earth fault relay settings must be configured in such a way that the relay nearer to the fault clears it faster than those further away.

To achieve proper coordination:

  • Set the TMS and pickup values considering the coordination time intervals (CTI) with upstream and downstream devices.
  • Choose appropriate characteristic curves (standard inverse, very inverse, etc.) based on system design.

4. Setting Procedure:

  1. Determine Rated Current of Transformer: Calculate the rated current of the transformer using the formula:

    Irated=Srated3×VratedI_{\text{rated}} = \frac{S_{\text{rated}}}{\sqrt{3} \times V_{\text{rated}}}
  1. where SratedS_{\text{rated}} is the transformer rating (in kVA or MVA) and VratedV_{\text{rated}} is the rated voltage.

  2. Select the Pickup Current: Set the relay pickup current to around 1.1 to 1.5 times the rated current.

  3. Set the TMS: Set the TMS value to ensure selective coordination. Use time-current curves to verify proper relay operation for various fault levels.

  4. Check System Coordination: Ensure the settings allow the relay to operate within the desired time frame and coordinate with upstream and downstream relays.

  5. Earth Fault Settings: Adjust the earth fault relay pickup and TMS to detect low-level faults, ensuring adequate protection against earth faults while avoiding nuisance tripping.

5. Advantages of IDMT Relays:

  • Selective protection: The inverse time characteristic provides selective protection, ensuring faster clearing of severe faults and slower tripping for minor, temporary overcurrent conditions.
  • Coordination: Easily adjustable settings allow for coordination between multiple relays, ensuring that only the nearest relay to the fault trips.
  • System stability: Time delay prevents nuisance tripping for transient overcurrent conditions, ensuring stable operation of the power system.

In conclusion, properly setting up an IDMT overcurrent and earth fault relay is essential for the effective protection of transformers and electrical systems. These settings should be done carefully, considering system load, fault levels, and coordination with other protection devices to ensure both equipment protection and system reliability.

Write about the 11kv/415v 1600kva Transformer IDMT Over Current _ Earth Fault Relay Setting 

The 11kV/415V 1600kVA transformer is a common step-down transformer used to reduce high voltage (11kV) to low voltage (415V) for distribution in industrial, commercial, or residential areas. It is crucial to protect this transformer from faults such as overcurrent (OC) and earth faults (EF) using protection relays. The Inverse Definite Minimum Time (IDMT) Overcurrent and Earth Fault Relay is typically used to provide this protection.

1. IDMT Overcurrent Relay Settings

The overcurrent relay protects the transformer against phase faults and overloading. The key parameters for setting an IDMT overcurrent relay are:

  • Current Setting (Pick-Up Current): This is the threshold at which the relay starts to operate. For a 1600kVA transformer, the full load current on the 415V side can be calculated as:

    Ifullload=16003×4152228AI_{full load} = \frac{1600}{\sqrt{3} \times 415} \approx 2228 \, A

On the 11kV side, the current will be:

I11kV=16003×1184AI_{11kV} = \frac{1600}{\sqrt{3} \times 11} \approx 84 \, A
Previous Post Next Post