How do you calculate the size of a diesel generator?

To calculate the size of a diesel generator, you need to determine the total electrical load it will need to supply. This involves a few steps:

1. List the Electrical Equipment

Gather a list of all the devices, appliances, or machinery the generator will power. Be sure to consider both the starting and running power requirements of each device.

2. Determine the Power Requirements

  • Starting Wattage: Many electrical devices, especially those with motors (like pumps or refrigerators), have a higher power requirement when starting. Check the specifications for each device.
  • Running Wattage: This is the continuous power requirement once the device is running.

Power can be expressed in either kilowatts (kW) or kVA:

  • Watts (W): 1 kW = 1000 watts.
  • kVA: The power in kilovolt-amperes accounts for power factor (usually assumed as 0.8 for most inductive loads). kW=kVA×Power Factor(PF)\text{kW} = \text{kVA} \times \text{Power Factor} (PF)

3. Add Up the Load Requirements

Add the starting and running wattages of all equipment. The total wattage gives the load in kilowatts.

4. Apply a Safety Margin

It's advisable to add a safety margin, typically around 10-30%, to ensure the generator can handle unexpected surges or future expansion of electrical load.

5. Convert to Generator Size

Convert the total power to the appropriate size for a generator, considering whether you're working in kW or kVA.

  • For example, if you need 50 kW of power, and the power factor is 0.8, the generator size would be:
kVA=kWPower Factor=500.8=62.5kVA\text{kVA} = \frac{\text{kW}}{\text{Power Factor}} = \frac{50}{0.8} = 62.5 \, \text{kVA}

Thus, a 62.5 kVA generator would be required.

Formula Recap:

Generator Size (kVA)=Total Load (kW)Power Factor\text{Generator Size (kVA)} = \frac{\text{Total Load (kW)}}{\text{Power Factor}}

Example Calculation:

If you're powering devices that total 20 kW of running load, and the power factor is 0.8, you would need:

Generator Size (kVA)=200.8=25kVA\text{Generator Size (kVA)} = \frac{20}{0.8} = 25 \, \text{kVA}

Adding a 20% margin:

25kVA×1.2=30kVA25 \, \text{kVA} \times 1.2 = 30 \, \text{kVA}

So, you would choose a 30 kVA generator.

Additional Considerations:

  • Single-Phase or Three-Phase Power: Ensure you account for whether the devices require single-phase or three-phase power.
  • Voltage Requirements: Ensure the generator provides the correct voltage for the equipment.

The size of a diesel generator is usually calculated based on the electrical power demand it needs to fulfill. The process involves several steps to ensure the generator can handle the load efficiently without overloading. The following formula and guidelines are typically used to determine the correct generator size:

Basic Formula:

The power required from the generator is calculated using the formula for electrical power:

P(kW)=V×I×3×PF1000P(kW) = \frac{V \times I \times \sqrt{3} \times PF}{1000}

Where:

  • P(kW)P(kW) = Power in kilowatts (kW)
  • VV = Voltage (Volts)
  • II = Current (Amps)
  • PF = Power factor (typically 0.8 for most industrial applications)

For single-phase systems, the formula becomes:

P(kW)=V×I×PF1000P(kW) = \frac{V \times I \times PF}{1000}

Steps for Calculation:

  1. List All Loads: Identify all equipment or systems that will be powered by the generator, including lights, motors, air conditioners, and other machinery.

  2. Determine Starting and Running Load: Equipment, especially motors, have two types of loads:

    • Running Load (kW): The continuous power needed during normal operation.
    • Starting Load (kVA or kW): The higher power needed when the equipment starts, especially for inductive loads like motors. The generator should be sized for the highest load, typically the starting load of the largest motor or inductive equipment.
  3. Sum the Power Requirements: Add the running load and account for the starting load to determine the total load in kW.

  4. Convert kW to kVA: Since generators are rated in kVA, the total kW should be converted to kVA using the power factor (PF):

    kVA=kWPFkVA = \frac{kW}{PF}

    For example, if the total power requirement is 100 kW and the power factor is 0.8, the generator size would be:

    kVA=1000.8=125kVAkVA = \frac{100}{0.8} = 125 \, kVA
  5. Add a Safety Margin: Typically, a safety margin of about 10-25% is added to the calculated size to account for unexpected additional loads or future expansion.

Example Calculation:

Suppose you need to power a facility that has the following equipment:

  • Lighting: 10 kW
  • Air Conditioning: 15 kW
  • Motor (running load): 20 kW, starting load: 60 kW

Total Load Calculation:

  • Running load = 10 kW (lighting) + 15 kW (A/C) + 20 kW (motor) = 45 kW
  • Starting load = 60 kW (for the motor starting load)

So, the generator must handle 60 kW at startup and 45 kW during normal operation.

Convert to kVA:

Using a power factor of 0.8:

  • Running load in kVA = 450.8=56.25kVA\frac{45}{0.8} = 56.25 \, kVA
  • Starting load in kVA = 600.8=75kVA\frac{60}{0.8} = 75 \, kVA

Since the generator must handle the starting load, the minimum generator size should be 75 kVA. After adding a safety margin of 10-25%, the final generator size would be around 82.5 - 93.75 kVA.

By following this process, you can ensure that the diesel generator is properly sized to handle both the running and starting loads of the system.