GENERAL INSTRUCTIONS FOR MAINTENANCE OF SWITCH YARD EQUIPMENT(Article)





(a)              External Cleaning

The insulators of the transformer bushings/ circuit breaker / CT / CVT / isolator shall be cleaned from salt and dirt/dust deposition together with the cleaning of the other insulators in the substation. The time interval for this cleaning shall be based on the polluting atmosphere. For installations with higher atmospheric/saline pollution, cleaning frequency may be increased and and these may be suitably protected against pollution.

(b)              Rust Protection

Some parts of the operating mechanism are made of steel and are surface treated against rust. In spite of the good rust protection, minor corrosion will occur after some years, especially when the breaker / isolator is standing in strong corrosive surroundings. The rust stains shall be sand papered away and new rust protection shall be painted or sprayed on. As rust protection, grease C or Tectyl 506 is recommended.

(c)                Lubrication

For lubrication, the lubricants recommended by manufacturers shall primarily be used. This is especially important in cold climates with temperatures below - 25°C.

The bearings of the breaker and operating mechanism of isolator and breaker are to be lubricated with grease G although these normally do not need lubrication before the major overhauls. Plain bearings in mechanism details such as arms, links and link gears are also to be lubricated with grease G. These bearings shall be regularly lubricated with a few drops of' oil B. The teeth in the gear shall be lubricated with grease G. Dryness of driving mechanism may lead to maloperation and failure.


(d)               Treatment of Contact Surfaces

The contacts of breaker / isolator / ground switch shall be treated according to the following directions:

·                    Silvered contact surfaces: Silvered contact surfaces shall be cleaned, if necessary, with a soft cloth and solvent (trichloro ethane). Steel brushing or grinding is not allowed.

·       Copper surface: Copper surfaces shall be clean and oxide free. If necessary, they

shall be cleaned with cloth and solvent (Trichloroethane) or steel brushing - After steel brushing, the surface shall always be cleaned of loose particles and dust.

·                    Aluminium surfaces: Aluminium contact surfaces shall be cleaned with steel brush or emery cloth. The surface is very thoroughly cleaned of particles and dust with a dry I cloth. After this, a thin layer of Vaseline is applied. This shall be done within 5 minutes after the cleaning. The joint shall be assembled within 15 minutes.

(e)             Moving Contact Surfaces

·                    Silvered: Cleaned if necessary, with soft cloth and solvent (trichloro ethane). No steel brushing.

·                    Non-silver coated: Cleaned as silvered surfaces, can be steel brushed. After steel

brushing they shall be thoroughly cleaned of loose particles and dust.

·                    Lubrication: Lubricant - Grease K is applied in a very thin layer on the surfaces of the male contact and the puffer cylinder. The superfluous grease is carefully removed.

 

2.                   TRANSFORMERS AND REACTORS

In order to provide long and trouble free service, it is important that a careful and regular supervision and maintenance of the transformer and its components is carried out. The frequency and extent of such a supervision and maintenance is dependent on the experience, climatic conditions, environment, service conditions, loading pattern etc. All work done on transformers should be recorded in history register for future reference. Efforts have been made to cover all important maintenance practices for transformers and reactors in this chapter with details of interpretation of test results.

I.                   General Supervision

(a)                Dirt and Dust

The external transformer surfaces shall be inspected regularly; and when required cleaned of dust, insects and other airborne dirt. Transformers/ reactors installed near polluting industry/cement plants, etc., need special care and more frequent cleaning of the bushings and other components. All Marshalling Boxes and OLTC cubicle are to be kept properly closed so that there will not be entry of dust inside, which is difficult to clean.

(b)              Rust and Treatment

A regular inspection is to be carried out of the external surface treatment of the transformer tank and radiators. Possible rust damages are removed and the surface treatment restored to original state by means of the primer and finish-paints of the transformer to minimize the risk of corrosion and its subsequent spreading. These checks also include looking for signs of oil leaks on gasket areas and welded areas containing oil. The touch-up paint as and when required as per site condition and re-painting is recommended once in five years. However transformers in coastal areas and more corrosive atmosphere may require more frequent painting.


(c)               Check for any Signs of Mechanical Damage

Checks must be carried out for mechanical damage to the fabrications and associated equipment. Particular attention should be given to vulnerable areas such as radiators. If damage is seen on the equipment, a decision must be taken as to its seriousness. It may be necessary to take corrective actions such as the replacement of an item of equipment.

 

(d)              Check on all Joints for Signs of Leakage

All joints, both welded and gasketed, must be checked for signs of oil leakage. If there is any doubt of a leak, the area must be cleaned of oil, using a suitable solvent (methyl alcohol) and sprayed with liquid chalk. This will promote the flow of the leak and give a good indication as to the exact location of the leak, if in fact there is one. If a leak is suspected on a gasket, the joint must be tightened until such time that it can be changed with a new gasket. If a leak is apparent at a welded joint once again clean the area and apply liquid chalk and allow to dry. This will highlight the point exactly if in fact there is a leak. It must be properly repaired with welding procedures when convenient. Prior to leaving the leak, it must be highlighted with a marker, or something similar, so it is not lost when permanent repair takes place.

Other areas commonly associated with oil leaks are drain plugs in radiators, valves in the oil management and cooling system and the gas and oil actuated relay.

(e)               Check for Oil Level

It is good practice to check all oil levels associated with the equipment. This will incorporate the expansion vessel and all oil filled bushings. Also the oil in the oil seal should be maintained. Some bushings in transformers will be below the conservator oil level and some above. If there is leakage in bushing at the oil end, the level will be low or high depending upon the level of conservator. External leak on bushing will lead to indicate low oil level. This is to be observed accordingly and if there is leak, action is to be initiated immediately as bushing failure may lead to failure of entire transformer.

 

OLTC oil conservators are always kept at lower level compared to the main conservator tank so that OLTC oil will not mix with main tank oil. An increase in level of oil in OLTC conservator tank indicates internal leakage and action is to be taken accordingly. After energizing of the transforn1er, a certain settling may appear in sealing joints. This applies especially to sealing joints with plain gaskets that are not placed in grooves. These should therefore be re-tightened. For correct torque for tightening the bolt, the manufacturer's recommendations are to be followed.


(f)                Check on the Surrounding Areas

Once all the checks are completed, a check should be made to ensure that all materials or tools, used for maintenance work, have been removed. All clothes and other debris must be disposed off. The transformer compound should be left in a clean and tidy condition.


II.                                        Checks on Breathers

(a)                                      Checks on Silica Gel Breather

In open breathing transformer, the breather plays active role in maintaining the transformer dry by admitting dry air when transformer breathes. In transformers having air cell or diaphragm, the breather ensures dry air inside the air cell or above the diaphragm. The silica gel inside the breather should become pink from bottom to top over a period of time. Any de-colorization at top or sides indicates leakage in container and need to be attended immediately. In order to prevent severe deterioration of the silica gel, it is recommended that it is replaced when half to two thirds of the silica gel has become saturated and turned pink in colour. Failure to do so will severely retard the drying efficiency of the breather. The silica gel can be reactivated by heating it to 130°C-140°C in a ventilated oven until it has achieved the bright blue colour. Check that the oil level is correct in the oil cup at the breather base and fill oil if the level is found low.

 

Note:   Do    not    exceed    the    temperature    stated    above    otherwise   the    colour impregnation will be destroyed and the silica gel will turn black.

Immediately after re-activation the loose silica gel must be placed in a sealed container to prevent absorption of moisture on cooling. The silica gel should be stored in sealed condition until required for use.

 

Self indicating (blue) silica gel contains the dye cobalt chloride which has been classified carcinogenic by an European Commission directive and ia a banned substance because of its potential health hazards. In Europe the silica gel breathers are to be disposed in 'Class l' disposal locations for hazardous waste products or incinerated.

An alternative to the blue self-indicating silica gel is SILICA GEL ORANGE with an organic indicator. The colour changes from orange to light yellow as it absorbs moisture. The specifications of silica gel orange are as shown below:

 

Parameter

Specification

Adsorption capacity

RH 50% (min)

20

RH 80% (min)

30

Appearance

Orange

Loss at heating up % (max)

4

 

Colour change

RH 50%

Light yellow

 

RH 80%

Colourless or Slight yellow

In view of above use of blue silica-gel may be phased out.


(b)                          Drycol Breather Check (If Available)

Drycol breathers are provided in some transformers where air cell is not provided. It condenses the moisture inside the conservator and brings it out as water droplets. Silica gel breather will also be provided for these transformers. The following checks need to be carried out for drycol breathers:

Operation of counter reading: Check on a regular basis that the counter is functioning. Record the figures each time a check is made so that a progressive check is recorded.

Defrost current condition indicates that water is still being ejected from the breather

Press the test button and check that a defrost current is being indicated. Check that the two red neon lights are ON and the amber neon light is OFF.

Release the test button and check that the counter has advanced one count and that freeze current is indicated.

III     Checks for Conservator

(a)              Visual Check for Conservator Oil Level

The transformer oil conservator is provided with an oil-level indicator graduated from 0 to 1 or min to 6 or "low" to "full" with grading depending on the manufacturer. Normally the face of oil gauge or dial of Magnetic oil level Gauge (MOG) is marked at the 35°C (or normal). These indications are relative to temperature of the operating equipment. The oil level indicated should be recorded along with top oil temperature.

If corrected oil level is normal, no additional action is required, whereas if it is above or below the normal level, it may be necessary to remove or add some oil. The correct oil-filling level is specified on an information plate that is placed on the transformer Rating plate panel. At an oil temperature of + 45°C, the conservator should be half filled. If the level exceeds the "full" oil must be drained off. If the value is "low" or "min", oil must be filled in.

 

(b)           Leakage Testfor Air Cell

Normally leakage test for air cell fitted inside the conservator is carried out before installing the conservator in its position or at the time of major overhaul. During service, the leakage in the cell or in the sealing of the conservator can be detected by the oil level in the prismatic oil level indicator, if provided, on the conservator. If there is no leakage, the prismatic oil level indicator will show "Full" oil level. However, in case of leakage, the oil level in the prismatic oil level gauge shall be lower than "Full" level.


For Releasing Air from Conservator Fitted with Air Cell

 

Pressurize the Air Cell up to the maximum pressure as specified by the manufacturer and open the air vent valves provided on the top of the conservator until oil starts coming out. Then close the valves. Release pressure from the Air Cell and refit breather.

For Releasing Air from Conservators Fitted with Diaphragm Type Air Sealing


Open the Air Release Valve provided on the top of the diaphragm and start filling oil into the conservator, preferably from the valve provided at the bottom of the conservator. Filling of oil from the oil filling valve at the bottom of the transformer tank is avoided because it may result in entry of air into the transformer which may get trapped in the winding and result in unnecessary accumulation of air in the Buchholz Relay at some later stage.

Continue filling oil into the conservator until it is full and oil starts coming out of the Air Release Valve. Close the Air Release Valve after ensuring that all the air has come out from the oil portion below the diaphragm.

 

Slowly drain the oil from the conservator until the oil level as indicated on the oil level gauge corresponds to the transfom1er oil temperature.

Before making the leakage test of air cell for the, transformer in service, oil should be drained out to the lower level of conservator. Apply pressure as specified by the manufacturers to inflate the air cell. Adjust the pressure after 6 hrs, if required. Check temperature and maintain the air cell at almost the same temperature for 24 hrs. If there is no loss of pressure during 24 hrs, it means the air cell is not having leak.

(c)             Caution

Any heating process like welding, grinding etc. are not allowed on the assembled conservator fitted with air cell diaphragm as it is highly sensitive to heat.

 

IV.             Check for Cubicle and Marshalling Kiosk and Valves

Marshalling Cubicle and Kiosk Check

The following need to be checked and ensured while inspecting and checking the

. Marshalling Boxes.

·                    Condition of paint

·                    Operation of door handles, Hinges

·                    Condition of door seal.

·                    Door switches

·                    Lights and heaters

·                    Thermostats

·                    Operation of heating and lighting switches

·                    Secure mounting of equipment

·                    Checking of tightness of cable terminations

·                    Checking of operation of contactors

·                    HRC fuses and their rating

·                    Operation of local alarm annunciation by pushing push buttons provided for lamp test, acknowledge, reset, system test, mute etc. to cover all system function.

·                    Source change over test check by putting off power sources alternatively.

·                    Check for plugs for dummy holes, glass windows and replacement, if found missing/ broken.

 

V.                Checks for Auxiliaries

(a)            Cooling System

The cooling surfaces of radiators shall be inspected regularly and when required cleaned of dust, insects, leaves or other air borne dirt. The cleaning is suitably carried out by means of water flushing at high pressure. Precaution should be taken to cover the fan- motor so that water may not go inside. Alternatively cleaning can be done with cleaning solution and cloth.


The fan-motors are provided with permanent - lubricated bearings and double sealing rings. The motor bearings are axially clamped with spring-washers. If the sound level of the fan increases, first tighten all mounting supports and in case any abnormal sound is noticed in fan motor, then action should be taken for repair! replacement.

 

(b)                Cooling System-Fans-Controls

Fan controls are designed to operate both manually and automatically with set temperature. Manual, Control is to be turned 'ON' to operate cooling system for checking. Oil pumps need to be checked by observing their flow gauges. Measurement of pump current reveals any abnormality. Any significant imbalance of current between the terminals greater than 15-20% is indicative of the problem with the pump motor. Checking for correct rotation of fans and pumps to be ensured as reverse rotation may not provide desired result.

(c)               Calibration of OTI / WTI

Temperature indicators in transformers are not only used for indication purpose they are used as protective device also. The accuracy of these devises is to be ensured for correct operation of alarm and tripping and also to prevent mal operation. The temperature bulb is to be removed from its well on the side/ top of transformer. Using a temperature controlled calibration instrument in oil bath the temperature of the bulb should be slowly raised in steps of 5°C and observed for temperature reading. If the temperature deviation is more than ± 5°C compared to the standard thermometer reading, the thermometers are to be replaced with healthy one.

(d)              Checking of Cooler Control, Alarm and Trip Settings

Setting of temperature should be as per approved scheme. Access the local winding/ oil temperature indicator and rotate the temperature indicator pointer slowly to the first stage cooling value (say 65°C). Check that the fans of those coolers set to first stage are operating. Continue rotating the pointer to the second stage cooling value (say 8O°C). Check that the fans of those coolers set to second stage are operating. Continue rotating the pointer to the alarm value (say 110°C). Check with the control room to ensure that the alarm signal has been received. Continue rotating the pointer to the trip value (say 125°C). Check with the control room to ensure that the trip signal has been received.

(e)                 Gas Pressure Relay

There are two types of gas pressure relays. The most common type is mounted at the transformer top body. Internal arcing in liquid filled electrical power equipment generates excessive gas pressures that can severely damage equipment and present extreme hazards to personnel. The gas pressure relay is intended to minimize the extent of damage by quickly operating and venting out the pressure. It will reset when the pressure becomes normal. A pointer is provided to indicate the operation of this relay and the relay is connected for tripping the transformer on operation. There will be oil spillage whenever the relay operates. Smaller transformers are provided with explosion vent where the diaphragm will rupture due to heavy internal pressure and releases the

pressure. The diaphragm needs to be replaced when it operates. There are some transformers fitted with sensitive sudden pressure relay, which operates on rate of change of differential pressure and trips the equipment.


(f)                 Buchholz Relays

The use of gas-operated relay as protection for oil-immersed transformers is based on the fact that faults as flashover, short-circuit and local overheating normally result in gas-generation. The gas-bubbles gathering in the gas-operated relay affect a float- controlled contact that gives an alarm signal.

For testing of the contact functions, buchholz relays are provided with a test knob on the cover. Unscrew the protective cap and press down the knob by hand. The spring loaded knob with a pin inside the relay actuates first the alarm device and then the tripping device. After testing, screw on the protective cap again.

Checking the operation of Buchholz relay in case of low oil level is carried out by closing step valve in both sides of the relay and draining of oil through oil drain valve provided in Buchholz relay. First alarm and then trip contact should operate to indicate healthiness.

To check the relay for oil surge, manufacturers recommendations for particular relays to be followed.

(g)              Bushings

Bushings are most failure prone in any transformer/ reactor. Failure of bushings could lead to the fire in transformer and total damage. For uniform voltage distribution across capacitance graded bushings, bushing porcelains shall be cleaned from dust and dirt during shutdown maintenance. In areas where the air contains impurities as salt, cement dust, smoke or chemical substances, shorter intervals are required.

VI.             Operational Checks and Inspection / Maintenance of Tap Changer

EHV Transformers are provided with tap changer to have voltage control. To enable operation of taps during service, On- Load Tap Changers (OLTC) are provided in EHV transformers. OLTCs may be located in either the high voltage winding or the low voltage winding, depending on the requirements of the user, the cost effectiveness of the application and tap changer availability. OLTC being a current interrupting device requires periodic inspection and maintenance. The frequency of inspection is based on time in service, range of use and number of operations.

(a)              Precautions

This testing shall be carried out during shutdown period and all testing shall be done under total de-energisation condition. Ensure the isolation of transformer for high voltage and low voltage side with physical inspection of open condition of the concerned isolators/ disconnectors. In case tertiary is also connected, ensure the isolation of the same prior to commencement of testing

(b)              Tap Changer Hand Operation

Check hand operation of the tap changer up and down the full range before electrical operation is attempted and that the handle interlock switch will not allow electrical operation while the handle is inserted. In addition where single phase tap changers are employed check their tap positions agree and are reached simultaneously at motor drive unit head. Continuity check should be done for any discontinuity during tap changing operation by connecting an analogue multi meter across HV and IV bushing in case of auto transformers and relevant winding in case of two winding transformers and change the tap positions from maximum to minimum.

(c)               Maintaining Circuit

Check the maintaining circuit for correct sequence by hand winding unit half way through a tap and then remove the handle. Energize the drive motor and ensure that the motor continues to drive the tap changer in the same direction.


(d)              Drive Motor

With the tap changer in mid position check the direction of rotation and measure the start and running currents in both the raise and lower mode of operation and record their values.

Set the motor overload to 10% above running current

(e)               Out of Step Relay

Move one tap changer is in the three-phase bank to be one position out of step with other two. Check the tap changer faulty alarm is activated. Repeat for other two phases.

Hold the raise and lower push buttons in following a tap change to ensure it only moves one tap at a time hence checking the step by step relay.

(f)              Tap Change Incomplete Alarm

Check the operation of the tap changer incomplete alarm, including the flag relay, by winding the unit by hand half way through a tap change and monitoring their correct operation and time to operate.

(g)            Remote Indication

Check the remote indication and control facility is proved to the outgoing terminals of the marshalling kiosk.

(h)              Tap Changer (Surge) Protective Relay

Check the tripping function of the relay. Open the cover and press button "Trip". Check that all circuit breakers of transformer operate properly. Press push Button "Reset" close the cover and tighten it.

(i)              Inspection and Maintenance of OLTCs

Normally the temperature of the OLTC compartment may be few degrees Celsius less than the main tank. Any temperature approaching or above that of the main tank indicates an internal problem. Prior to opening the OLTC compartment, it should be inspected for external symptoms of potential problems. Such things as integrity of paint, weld leaks, oil seal integrity, pressure relief device and liquid level gauge are all items which should be inspected prior to entering the OLTC.

Following de-energisation, close all valves between oil conservator, transformer tank and tap-changer head, then lower the oil level in the diverter switch oil compartment by draining of oil for internal inspection. Upon opening the OLTC compartment, the door gasket should be inspected for signs of deterioration. The compartment floor should be inspected for debris that might indicate abnormal wear and sliding surfaces should be inspected for signs of excessive wear.

 

Finally, the tap selector compartment should be flushed with clean transformer oil and all carbonization, which may have been deposited, should be removed. Min BDV should be 50 kV and moisture content should be less than 20 PPM.

Dissolved Gas Analysis (DGA)

Transformer undergoes electrical, chemical and thermal stresses during its service life which may result in slow evolving incipient faults inside the transformer. The gases generated under abnormal electrical or thermal stresses are hydrogen (H2), methane(CH4), ethane(C2H6), ethylene (C2H4), acetylene (C2H2), carbon_monoxide (CO), carbon dioxide (CO2), nitrogen (N2) and oxygen (02) which get dissolved in oil. Collectively these gases are known as FAULT GASES, which are routinely detected and quantified at extremely low level, typically in parts per million (ppm) in dissolved Gas Analysis (DGA). Most commonly method used to determine the content of these gases in oil is using a vacuum Gas Extraction apparatus/ Head Space Sampler and gas chromatograph.


DGA is a powerful diagnostic technique for detection of slow evolving faults inside the transformer by analyzing the gases generated during the fault which gets dissolved in the oil. For Dissolved Gas Analysis to be both useful and reliable, it is essential that sample taken for DGA should be representative of lot, no dissolved gas be lost during transportation and laboratory analysis be precise and accurate. Effective fault gas interpretation should basically tell us first of all, whether there is any incipient fault present in the transformer. If there is any problem, what kind of fault it is. Whether the fault is serious and the equipment needs to be taken out of service for further investigation.

DGA can identify deterioration of insulation oil and hot spots, partial discharge, and arcing. The health of oil is reflective of the health of the transformer itself. DGA analysis helps the user to identify the reason for gas formation and materials involved and indicate urgency of corrective action to be taken.

 

The evolution of individual gas concentrations and total dissolved combustible gas (TDCG) generation over time and the rate of change (based on IEC 60599 and IEEE C 57-104 standards) are the key indicators of a developing problem. Some of the recognized interpretation techniques are discussed below:

Individual Fault Gases Acceptable Limits

When no previous DGA history of Transformer is available, to ensure that a transformer is healthy or not, the DGA results are compared with the gassing characteristics exhibited by the majority of similar transformer or normal population. As the transformer ages and

 

gases are generated, the normal levels for 90% of a typical transformer population can determined. From these values and based on experience, acceptable limits or threshold levels have been determined as given in table (as per IEC 60599) below:-

 

Transformer Type

Fault Gases (in µ1/1)

 

No OLTC

H2

CH4

C2H6

C2H4

C2H2

CO

CO2

60-150

40-110

50-90

60-280

3-50

540-900

5100-

13000

Communicating OLTC

75-150

35-130

50-70

110-250

80-270

400-850

5300-

12000

 

The values listed in this table were obtained from specific networks. Values on other networks may not exactly indicate healthiness.

 

“Communicating OLTC” means that some oil and/or gas communication is possible between the OLTC compartment and the main tank or between the respective conservators. These gases may contaminate the oil in the main tank and affect the normal values in these types of equipment. “NO OLTC” refers to transformers not equipped with an OLTC, or equipped with an OLTC but not communicating with or leaking to the main tank.

 

However it is improper to apply threshold level concept without considering the rate of change of the gas concentration in Dissolved Gas Analysis. When an abnormal situation is indicated by above table, a testing schedule is devised with increased sampling frequency.


Total Dissolved Combustible Gas (TDCG) Limits

 

TDGC limits, PP

Action

<or = 720

Satisfactory operation, Unless individual gas acceptance values

are exceeded

721-1920

Normal ageing/slight decomposition, Trend to be established to

see if any evolving incipient fault is present.

1921-4630

Significant decomposition, Immediate action to establish trend

to see if fault is progressively becoming worse.

>4630

Substantial decomposition, Gassing rate and cause of gassing should be identified and appropriate corrective action such as

removal from service may be taken.

 

TDCG includes all hydrocarbons, CO and H2 and does not include CO2 which is not a combustible gas.

Evaluation of Gases

The temperature at which the fault gas evolves is given in the table below:


Relationship with temperature

Methane CH4>120oC 

Ethane (C2H6)>120oC 

Ethylene (C2H4)>150oC

Acetylene (C2H2)>700oC


Faults Associated with Different Gases

 

Oil Overheating

C2H4, C2H6,CH4

Overheated Cellulose

Traces of acetylene with smaller quantity of Hydrogen may be evolved. Large quantity of Carbon-Di-Oxide (CO2) and Carbon Monoxide (CO) are evolved from overheated cellulose. Hydrocarbon gases such as Methane and Ethylene will be formed if the fault involved oil impregnated structure.

CO

Partial discharge in Oil (Corona)

Ionization of high stressed area where gas/vapour filled voids are present or ‘wet spot’produces Hydrogen and methane and small quantity of other hydrocarbons like ethane and

ethylene. Comparable amounts of carbon mono-oxide and di- oxide may result due to discharges in cellulose.

H2,CH4

Arcing in Oil

Large amount of Hydrogen and acetylene are produced with minor quantities of methane and ethylene in case of arcing between the leads, lead to coil and high stressed area. Small amounts of carbon mono-oxide and di-oxide may also be

formed, if fault involves cellulose.

C2H2,H2


It is to be understood that there is no definite interpretation method available, which can indicate the exact location and type of the! fault. The different interpretation methods only provide guidelines to make expert interpretation about the equipment. Apart from the DGA results various other factors are taken into consideration such as past history of the transformer, grid condition, loading patterns, voltage and frequency profile, etc.

 

 

3.                  CIRCUIT BREAKERS

Circuit breakers basically consists of two main parts, the interrupting chambers and the operating mechanism. The interrupting chambers normally do not require routine preventive maintenance other than cleaning but operating mechanism do require proper upkeep.

 (a)            Interrupting Chamber

Circuit breaker interrupting chamber is an enclosed unit mostly filled with oil or SF6 gas. Lower voltage Circuit breakers have vacuum interrupting chambers also. There is stress on the contacts during fault current interruption and damages may happen in arcing contacts or main contacts. The breaker interrupting chamber is recommended to be opened only based on condition monitoring tests or as per advice of the manufacturers.

(b)              Operating Mechanisms

Normally circuit breakers have pneumatic, hydraulic and spring operating mechanisms. As operating force is required for closing and tripping of circuit breakers, there can be combination of these mechanisms in one circuit breaker. Since operating mechanisms have a number of moving parts, they need more maintenance such as

 

greasing, lubrication, cleaning, setting of limit switches, etc. Compressors/ oil pumps/ spring charging motors also require maintenance. Other maintenance on particular operating mechanism such as air compressor maintenance, nitrogen priming pressure checking in hydraulic mechanism, checking of over travel, checking of gaps in operating plunger of close/ trip coils etc. are to be carried out as the case may be and as specified by the manufacturers.

(c)                SF 6 Gas

Most of the higher voltage circuit breakers adopt SF6 in interrupting chamber. The density of SF6 gas is about five times that of air and heat dissipation is also much more than air. At atmospheric pressure, dielectric strength of SF6 gas is about 2.4 times that of air and at about 3 kg/cm2 it is same as that of oil. As SF6 is Green House gas, it needs to be handled carefully and should not be let to the atmosphere.

(d)            Emptying and Re-filling of Gas

The breaker is evacuated by means of the gas treatment equipment that purifies and also compresses the gas for storage, so that it can be reapplied. For economic and ecologic reasons, SF6 contained in electrical equipments, should not be vented into atmosphere. Prior to the gas removal, the quality of the SF6 gas should be tested.

Operational contamination should be absorbed with suitable filter unit provided in the gas handling plant. Such filters/ sieves should already be installed into the SF6 gas maintenance/handling unit. When SF6 is suctioned from a gas compartment, the gas is passed automatically through filters, which dry and purify the gas.


(e)             Evacuation of SF6 Gas Circuit Breakers

After maintenance/overhaul of the circuit breaker, it should be evacuated by vacuum PUI1l] before filling in the SF6 gas so that SF6 gas does not mix with ambient air and also humidity and dust particles are removed from the Breaker. With vacuum pump, a final vacuum must be reached less than 5 mbar.

 

4.                  PREVENTIVE MAINTENANCE OF CURRENT TRANSFORMERS

(a)              Visual Inspection

Current transformers are normally filled with oil and have oil impregnated paper insulation for both primary and secondary winding. Careful inspection is to be made for any trace of oil leakages. Oil leakages are more prone through cemented joints or secondary terminal box due to improper sealing of terminal studs. As CTs have less oil quantity small leakage may lead to exposure of paper insulation and subsequent moisture absorption.

If bellows are provided in CTs, the position of bellow indicates either leakage of oil or expansion due to internal gas generation. Both the conditions are serious for the life of the CTs and immediate action to be initiated for rectification.

 

Visual inspection is also to be carried out on the healthiness of terminal connections, condition of porcelain, development of cracks, chippings, cleanliness of insulator surface etc.

(b)              Maintenance of Gaskets

Marshalling boxes, CT terminal boxes are to be properly sealed to prevent any dust, rain water and insects. Door gaskets are to be changed periodically to give proper sealing. All door bolts/ latches are to be properly tightened and never left loose.

(c)               Secondary Terminals Connections

Stud type terminals are preferred in Marshalling box cable terminals. This gives better grip even if more than one wire is connected to one terminal. But pin type terminals are also provided in some cases. Since tightness of wires may become loose due to vibration, climatic condition, it is required to check tightness of terminals periodically to avoid maloperation/ non-operation due to improper contacts. All terminals of unused CT secondary terminals are to be properly shorted to avoid development of abnormal voltage and subsequent failure of CTs. The tan δ test tap is to be properly earthed to avoid damage to insulation.

Primary Terminals

Thermovision scanning indicate proper connection of primary terminal. If thermovision is not carried out, physical checking of terminal connection is to be done with proper torque. All corona shields are to be provided and any damaged corona shield to be replaced with new one. As CT primary carries heavy current, any loose joint may lead to arcing and welding of terminal connectors.

5.                  CAPACITANCE VOLTAGE TRANSFORMERS/ POTENTIAL TRANSFORMERS/ CAPACITOR COUPLING

(a)              Visual Inspection

The bel10ws provided in most of the CVTs are not visible from outside. CTs/ CVTs and CC are also oil fil1ed equipments and oil leak is to be observed. If oil leak is observed in anyone stack, the entire CVT is to be replaced. CVTs are tuned units and replacement of anyone stack is not recommended to avoid phase angle errors.


(b)              Electro-Magnetic Unit

Electro-Magnetic Unit (EMU) of CVT houses the secondary transformer, Compensating reactor and ferro resonance suppression circuit. The colour of oil indicated through the gauge: glass gives some indication of the healthiness of the internal components. Any abnormal heating may also be observed through Thermovision scanning.

(c)               Secondary Voltage

Deviation in secondary Voltage of CVT is clear indication of failure of capacitor elements. Necessary action to be taken to replace CVT if secondary voltage in anyone CVT is abnormal (may be +2V and -4V). Continuing the equipment in service beyond this stage may lead to failure/ bursting of CVTs.

(d)              Other Maintenance

Maintenance of Marshalling box gaskets, tightening of secondary terminal connections and tightening of primary terminal connections, etc., are also to be ensured for healthy operation. It is to be ensured that al1 extra holes at Marshalling boxes are properly plugged and kept vermin proof. The anti-condensation heater and the thermostat are to be kept in working condition to keep inside of the panel dry.

 

 

6.                  DISCONNECTORS/ISOLATORS

 

Disconnectors have main current carrying arms and operating mechanism for connection and' disconnection. Being are off-line devices, they are normal1y air break type. Normally horizontal double break, Horizontal center break, Pantograph, Vertical break Disconnectors are in use for EHV isolations.

The alignment of Disconnectors is very important for smooth operation. The limit switches, the healthiness of auxiliary contacts needs to be checked periodical1y. The main contacts are to be inspected and made smooth if any pitting marks seen. The corona shields are to be kept smooth and shining and checked for tightness of fitting. Damaged

corona rings should be replaced. All moving parts are to be lubricated for smooth operation. The gear mechanism and motor normal1y do not require any maintenance and manufacturer's recommendation should be referred for maintenance of gears.

Earth Switches

The earth switch is a safety device and smooth operation is to be ensured by proper alignment. The earth blade contacts are to be cleaned properly for proper contact and contact resistance to be measured to ensure healthiness. The earth connection from blade to earth is to be carefully checked. All the joints to be tightened and flexible copper braid connections are provided and healthiness is to be ensured. All moving parts to be lubricated for smooth operation.

 

7.                  LIGHTING ARRESTER/SURGE ARRESTERS

Surge arresters are to be maintained to give protection to other connected switchyard equipments. Cleaning of porcelain insulators is very much required for uniform voltage distribution. Voltage grading rings are to be properly positioned and checked for tightness and any damaged rings to be replaced. Healthiness of surge monitors is to be checked and if found defective the same may either be replaced with healthy one or shorted to minimize earth resistance. Healthiness of earth connections to be checked as it plays a vital role on the operation of the surge arrester. Normally it is not recommended that if one stack fails it is replaced with healthy stack. It is always a good practice to change the entire arrester as the stressed stacks will start failing along with the new stack.


8.                  BATTERY AND BATTERY CHARGERS

Substations generally use Lead Acid batteries/for DC batteries for DC supply. More and more maintenance free batteries are now offered for substation applications which require less maintenance. As DC system is vital part of substation during emergency, upkeep of battery system is very important.

Cell containers are to be kept always clean to avoid surface leakage. Any leakage is to be attended immediately. Vaseline / white petroleum jelly is to be applied on battery terminal and inter-cell connectors, nuts and bolts to avoid sulphate deposit. The rubber seal at the base of the terminals and on cell lid is to be fitted properly and to be replaced if damaged. All connections are to be checked for tightness.

 

All vent plugs and level indicators to be maintained for healthiness. Maintaining level of electrolyte in flooded cells is of very important to avoid sulphation and permanent damage of the cells. Distilled water is to be added to make up to the level.

If VRLA battery is used, the battery room temperature is to be maintained using air conditioner as the temperature plays vital role on the performance of the battery.

(a)              Battery Chargers

Battery charger is to be maintained for keeping the battery always charged and also to supply normal DC load for operation. If the charge / discharge ammeter does not show current on the charge side, then the float charger is not giving output. Defect should be located and corrected. In case of failure of float charger, the boost charger may be used as float charger as per design.

Charger panel is to be kept clean, free from dust and all terminals to be checked periodically for tightness. The battery maintenance and condition monitoring is to be carried out as per schedule to keep the DC system in healthy condition.

(b)              BATTERY CAPACITY TESTING

This procedure describes the recommended practice of capacity testing by discharge in the battery. All testing should follow the safety requirements.

 

(c)               INITIAL REQUIREMENTS

The following list gives the initial requirements for all battery capacity tests except otherwise noted.

(a)  Equalize the battery if recommended by the manufacturer and then return it to float for a minimum of 72 h, but less than 30 days, prior to the start of the test.

(b)  Check all battery connections and ensure that all connections are proper and clean.

(c)  Record the specific gravity and float voltage of each cell just prior to the test.

(d)  Record the electrolyte temperature of lO% or more of the cells to establish 31 average temperature.

(e)  Record the battery terminal float voltage

(f)   Take adequate precautions (such as isolating the battery to be tested from the batteries and critical loads) to ensure that a failure will not jeopardize other systems or equipment.


*

Post a Comment (0)
Previous Post Next Post