Furnace Transformer Name Plate Details

Here’s a detailed explanation of your Furnace Transformer Nameplate:


🔍 Transformer Overview

Field Value Explanation
Type of Phase 3-phase transformer
Connection Type AN Likely manufacturer’s internal code (not standard notation)
KVA Rating 300 KVA Transformer capacity: can handle 300,000 VA (or 300 kVA)
Primary Voltage 380 / 400 / 420 V Input voltage (star-connected) — selectable based on tap
Secondary Voltage 60 V Output voltage (delta-connected) — for furnace heater circuits
Primary Current 456 / 433 / 412 A Current drawn at respective primary voltages (depends on tap selected)
Secondary Current 2887 A Very high current — furnace heaters draw large current at low voltage
Impedance Not specified here (normally %Z) Usually shows short circuit impedance (not printed here)
Frequency 50 / 60 Hz Operates on standard utility frequency (India = 50 Hz)
Cooling Type Air Cooled Natural air cooling — no oil or fan system
Vector Group Yd11 Y = star primary, d = delta secondary, 11 = 330° phase shift

🧮 Vector Group: Yd11

  • Primary winding: Star (Y)
  • Secondary winding: Delta (d)
  • Phase Shift: 11 o’clock position → 330° shift

Used in applications like furnaces where:

  • Load needs low voltage, high current
  • Isolation and phase shift are useful

🧊 Cooling Info

Field Value
Cooling Type Air Cooled
Core & Winding 1023 Kg
Total Mass 1388 Kg

This is a dry-type transformer, cooled by natural air. Total mass includes casing, terminals, etc.


🏷️ Markings & Terminals

➤ Primary (STAR-connected):

  • Voltage taps: 380V, 400V, 420V
  • Neutral available
  • Used for 3-phase power input

➤ Secondary (DELTA-connected):

  • Output voltage: 60 V between phases
  • No neutral — only line-line available
  • Suited for heaters in delta

🏭 Application Fit:

This transformer is specially built for industrial furnaces:

Feature Purpose
🔥 Low voltage, high current (60 V / 2887 A) To supply power to resistive heating elements
🧊 Air cooled Easy to maintain, ideal for indoor control rooms
🔄 Delta secondary Perfect for 3-phase heater bank in delta
🛡️ Yd11 vector Helps isolate furnace system from supply and reduce harmonics impact















✅ Summary:

  • 300 kVA air-cooled transformer
  • Primary: 380–420 V star
  • Secondary: 60 V delta, high current (2887 A)
  • Used to power 3-phase delta-connected heaters in a vacuum furnace
  • Vector group Yd11 ensures isolation and controlled phase shift


*