Relay setting calculation for generator relay panels is a crucial step in ensuring the safe, reliable, and efficient operation of power generation systems. Generator protection relays monitor critical parameters such as overcurrent, over/under-voltage, frequency, and more. They respond to abnormal conditions by isolating the generator from the power system, preventing equipment damage and minimizing power disruptions. Here’s a detailed guide to the relay setting calculations for generator relay panels.
1. Purpose of Generator Protection Relays
Generator protection relays detect various faults and abnormal conditions to:
- Protect the generator from electrical and mechanical damage.
- Ensure stability and continuity of the power system.
- Safeguard personnel and connected equipment.
Generator relays monitor parameters like current, voltage, frequency, and temperature. They trigger corrective actions, such as tripping circuit breakers, when these values exceed safe limits.
2. Types of Protection and Associated Relays
Overcurrent Protection (51G/50G)
- Protects the generator from excessive current due to faults or overload conditions.
- Typically, two settings are used: one for instantaneous tripping (50G) and another for time-delayed tripping (51G).
Over/Under Voltage Protection (27/59)
- Overvoltage protection (59) responds to excessive voltages that can damage the generator's insulation.
- Undervoltage protection (27) detects low voltage, which could indicate problems with excitation or external faults.
Over/Under Frequency Protection (81O/81U)
- Over-frequency (81O) and under-frequency (81U) relays protect against deviations from nominal frequency, which can harm the generator and other equipment.
Reverse Power Protection (32)
- Reverse power protection detects when the generator starts consuming power rather than supplying it, often due to loss of prime mover input.
Differential Protection (87G)
- Detects internal faults by comparing currents at the generator terminals and neutral. Differential protection responds quickly to internal faults with high sensitivity.
Loss of Field Protection (40)
- Protects against loss of excitation, which could cause the generator to draw reactive power from the system, potentially damaging the generator.
Negative Sequence Protection (46)
- Protects the generator from unbalanced loads, which could cause heating and damage the rotor.
3. Key Parameters for Relay Setting Calculations
Generator Rated Current (Igen)
- Calculated based on generator rated power (S) and rated voltage (V): Igen=3
CT Ratio and PT Ratio
- Relay settings are typically calculated based on the secondary current or voltage provided by current transformers (CTs) and potential transformers (PTs). Understanding CT and PT ratios is critical to setting accurate relay values.
System Fault Current and Impedance
- Fault current values are used to set overcurrent, differential, and other protection relays. System impedance and fault impedance data aid in calculating expected fault levels at various locations.
4. Relay Setting Calculations
Overcurrent Relay Setting (50/51)
- Instantaneous Overcurrent (50G): Set based on maximum allowable fault current without delay. Typically set to 1.2–1.5 times the rated current.
- Time-Delayed Overcurrent (51G): Set to trip the generator under sustained overload. Delay settings are typically based on the thermal characteristics of the generator, using a time-current curve to coordinate with downstream protection.
Over/Under Voltage Relay Setting (59/27)
- Overvoltage (59): Usually set between 110% and 120% of the nominal voltage to protect insulation.
- Undervoltage (27): Set to around 80%–90% of the nominal voltage to prevent operation under poor voltage conditions that can lead to voltage instability.
Over/Under Frequency Relay Setting (81O/81U)
- Overfrequency (81O): Set slightly above the nominal frequency (e.g., 50.5–51 Hz for a 50 Hz system) to protect against an increase in speed.
- Underfrequency (81U): Set slightly below the nominal frequency (e.g., 49–49.5 Hz for a 50 Hz system) to protect against grid instability.
Reverse Power Relay Setting (32)
- Reverse power setting is calculated as a percentage of the generator's rated power, usually between 2%–5%. This setting protects against backfeeding when the generator loses prime mover input.
Differential Relay Setting (87G)
- Differential protection typically has high sensitivity and quick response. The relay setting is often set at 10%–20% of the generator rated current to detect low-level internal faults.
Loss of Field Relay Setting (40)
- This relay operates when reactive power flow reverses or falls below a certain threshold, indicating excitation loss. The relay setting is generally set around 50%–70% of the rated field current.
Negative Sequence Relay Setting (46)
- Negative sequence current setting typically ranges from 10%–15% of the generator rated current. This setting protects against unbalanced loads that can cause rotor overheating.
5. Time Delay Settings
- Coordination: Relay settings should coordinate with other upstream and downstream devices to avoid unnecessary tripping. Time delays are often added to overcurrent and differential relays to prevent tripping during transient conditions.
- Load Shedding and Frequency Stability: For under-frequency relays, time delays are set to allow the system time to recover or shed load if required.
6. Calculation Example: Overcurrent Relay Setting
- Example Data:
- Generator rated power: 100 MVA
- Rated voltage: 11 kV
- CT ratio: 1000:5
- Calculate Generator Rated Current (Igen): Igen=3
- Secondary Current (Isec): Using a CT ratio of 1000:5: Isec=10005,248×5=26.24 A
- Setting Instantaneous Overcurrent (50G): For an instantaneous setting of 1.2 times the rated current: Setting=1.2×26.24≈31.5 A
- Setting Time-Delayed Overcurrent (51G): Using time-current curve, set to allow tripping for sustained overloads, with a delay for coordination.
7. Relay Coordination and System Protection
- Coordination with Downstream Protection: Generator relay settings must coordinate with downstream protection to ensure that the closest device to a fault trips first. This minimizes system disruption.
- Interfacing with Breakers and Switchgear: Relay settings should be compatible with the operating characteristics of circuit breakers, ensuring they can handle expected fault currents and respond within appropriate time limits.
8. Testing and Validation
- Relay Testing: Use test equipment to validate relay settings under simulated fault conditions. Tests include primary injection testing, secondary injection testing, and end-to-end testing.
- System Simulation: Digital simulations using software like ETAP or PSCAD help verify relay settings and coordination under various scenarios, such as load changes, faults, and stability events.
Conclusion
Setting relays for generator protection requires careful calculation to ensure effective fault detection and isolation while maintaining system stability. Relay settings for overcurrent, voltage, frequency, and reverse power are calculated based on generator ratings, fault analysis, and coordination with other protective devices. Accurate relay setting calculations prevent unnecessary trips, reduce downtime, and ensure safe operation of the generator within the power system.