Electrical Protection Fault Calculations (Pdf Copy)

 INTRODUCTION

A power system is normally treated as a balanced symmetrical three-phase network. When a fault occurs, the symmetry is normally upset, resulting in unbalanced currents and voltages appearing in the network. The only exception is the three-phase fault, which, because it involves all three phases equally at the same location, is described as a symmetrical fault. By using symmetrical component analysis and replacing the normal system sources by a source at the fault location, it is possible to analyse these fault conditions.

For the correct application of protection equipment, it is essential to know the fault current distribution throughout the system and the voltages in different parts of the system due to the fault. Further, boundary values of current at any relaying point must be known if the fault is to be cleared with discrimination. The information normally required for each kind of fault at each relaying point is:

i. maximum fault current
ii. minimum fault current
iii. maximum through fault current
To obtain the above information, the limits of stable generation and possible operating conditions, including the method of system earthing, must be known. Faults are always assumed to be through zero fault impedance.

You have to wait 10 seconds.

Download Timer

*

Post a Comment (0)
Previous Post Next Post