Electrical Standard acceptable technical values(article)

 

 

1.1

Fresh Transformer oil before filling in Transformer

Parameters

Standard Values (Acceptable

range)

Source

(a) Appearance

Clear and transparent and free from

suspended matter or sediments

IS 335 1993

(b) Density at 29.50 C

0.89 g/cm3 (Max)

IS 335 1993

(c) Kinematic Viscosity at 270 C at

400 C, Max

27 cSt (Max) under consideration

IS 335 1993

(d) Interfacial Tension (IFT) 270 C

0.04 N/m (Min)

IS 335 1993

(e) Flash point, Pensky marten (Closed)

140 0 C (Min)

IS 335 1993

(f) Pour point

- 60 C (Max)

IS 335 1993

(g) Acidity (Neutralisation Value)

 

 

(i) Total acidity

0.03 mg KOH/ g (Max)

IS 335 1993

(ii) Inorganic acidity/ alkalinity

Nil

IS 335 1993

(h) Corrosive Sulphur

Non Corrosive

IS 335 1993

(i) Di-electric strength (Breakdown voltage)

 

 

(i) New unfiltered oil

30 kV, rms (Min)

IS 335 1993

(ii) After filtration

60 kV, rms (Min)

IS 335 1993

(j) Dielectric Dissipation Factor (Tan

) DDF at 900 C

0.002 (Max)

IS 335 1993

(k) Specific Resistance (Resistivity)

 

 

(i) at 900 C

35*1012 Ω –cm (min)

IS 335 1993

(ii) at 270 C

1500*1012 Ω –cm (min)

IS 335 1993

(l) Oxidation stability

 

 

(i) Neutralization value after

oxidation

0.40 mg KOH/g (Max)

IS 335 1993

(ii) Total Sludge after Oxidation

0.10% by weight (Max)

IS 335 1993

(m) Ageing Characteristics after Acceleration ageing (open breaker

method with copper catalyst)

 

 

(i) Specific Resistance

(Resistivity)

 

 

at 270 C

2.5*1012 Ω –cm (min)

IS 335 1993

at 900 C

0.2*1012 Ω –cm (min)

IS 335 1993

(ii) Dielectric Dissipation Factor ( Tan delta) at 900 C

0.2 (Max)

IS 335 1993

(iii) Total Acidity

0.05 mg KOH/ g (Max)

IS 335 1993

(iv) Total Sludge

0.05% by weight (Max)

IS 335 1993

(iv) Total Sulphur

0.15% (Max)

IEC 60296-2003

(n) Water content of new unfiltered

oil

50 ppm (Max)

IS 335 1993

(o) S. K. Value

4 to 8% by mass (Max)

IEC 60296, 2003

(q) Presence of Oxidation Inhibitor

Oil shall not contain antioxidant additives. Value of 0.05% by mass

(Max) shall be treated as absence of

IS 335 1993


 

 

DBPC Phenolic type inhibitor

 

(r) PCB content (Polychlorinated Bipheyls)

Not detectable 0.1 mg/kg (Max)

IEC 60296, 2003

(s) Dissolved Gas Analysis (DGA)

Not applicable

IS 335 1993

(t) 2 – furfural (Furan Analysis, Test method IEC 61198:1993)

0.1 mg/kg (Max)

IEC 60296, 2003

(u) Furfural (Aging criteria for oil immersed Power Transformer)

Warning Trouble 1.5 ppm 15 ppm

CIGRE DOC. No.

227 Life Management Technique for Power Transformer

Page 107

(v) Total Furan Content

250 parts per billion (ppb)

Transformer Diagnostic USBR,

june 2003, Page 15

Additional Requirement for inhibited oil

 

 

Inhibitor content (Antioxidation additive content)

DBPC (Ditertiary Butyl Paracersol) DBP (Ditertiary Butly Phenol)

Minimum 0.08 % by mass and maximum 0.4% by mass

Inhibitor content determination ( Test Mehod:IS 13631)

IEC 60296, 2003

Minimum 0.15 % by mass and

maximum 0.3% by mass

Nynas and shell

Inhibited oil

 

 

1.2

Transformer oil for in-service Transformer

 

Oil Parameters

At the time of first Charging.

During O&M

 

(a) Appearance

Clear, free from sediment and

suspended matter

Clear without visible

contamination

IS 1866

- 2000

(b) Break Down Voltage (BDV) (GAP

2.5 mm) min

40 kV for < 72.5 kV

50 kV for 72.5 to 170 kV

60 kV for > 170 kV

30 kV for < 72.5 kV

40 kV for 72.5 to 170 kV

50 kV for > 170 kV

IS 1866

- 2000

(c) Water content (Moisture) (Max)

20 ppm for < 72.5 kV

15 ppm for 72.5 to 170 kV

10 ppm for > 170 kV

No free moisture for<72.5 kV 40 ppm for 72.5 to 170 kV

20 ppm for > 170 kV

IS 1866

- 2000

(d) Acidity (Neutralization value

( Max)

0.03 mg KOH/g

0.3 mg KOH/g

IS 1866

- 2000

(e) Sediment &

Sludge (Max)

0.01% by mass

0.02 by mass

IS 1866

- 2000

(f) Resistivity

 

 

 

(i) Resistivity at 200

C (Min)

 

1*1012 Ohm-cm

IS 1866

- 2000

(ii) Resistivity at 900

C (Min)

6*1012 Ohm-cm

0.1*1012 Ohm-cm

IS 1866

- 2000

(g) Dielectric Dissipation factor at 900C and 40-60 Hz

(Tan Delta/ power factor) (Max)

0.015 for < 170 kV

0.01 for ε170 kV

1.0 for <170 kV

0.2 for    170 kV

IS 1866

- 2000

(h) Inter Facial Tension (IFT) AT

270 C (Min)

35 mN/m

15 mN/ m

IS 1866

- 2000

(i) Flash Point (Min)

1400C

Max decrease of 150C from initial

value

IS 1866

- 2000


 

(j) Density at 29.50C

(Max)

0.89 g/cm3

Not Essential

IS 1866

- 2000

(k) Kinematic Viscosity at 270C

(Max)

27 cSt

Not Essential

IS 1866

- 2000

(l) Pour point (Max)

-60C

Not Essential

IS 1866

- 2000

(m) Oxidation stability of

uninhibited old

 

 

 

(i) Neutralization

value (Max)

0.4 mg KOH/g

Not Essential

IS 1866

- 2000

(ii) Sludge (Max)

0.1% by mass

Not Essential

IS 1866

- 2000

Additional requirement for

inhibited oil

 

 

 

(n) Oxidation

Stability of inhibited oil

Minimum 0.08% by mass and maximum 0.4% by mass

Not Essential

IEC 60296,

2003

 

1.3

Dissolved Gas Analysis (DGA)

 

Typical rates of gas

increase for power transformers

Values in milliliters per day

IEC: 60599-1999 See

note Below

Hydrogen (H2)

<5

Methane (CH4)

<2

Ethane (C2H6)

<2

Ethylene (C2H4)

<2

Acetylene ((C2H2)

<0.1

Carbon Monoxide

(CO)

<50

Carbon dioxide (CO2)

<200

Equation to calculate the rate of gas increase as per IEC: 60599 – 1999 Rate – (Y2-Y1)m/{>(d2 – d1)} m1/ day

Where

Y1 = is the reference analysis Y2 = is the last analysis

(Y2-Y1) – is the increase in micro litre per litre. M = is the mass of oil, in kilograms

P = is the mass density, in kilograms per cubic metre. d2 = is the date for Y1

d1 = is the date for Y2

1.4

Transformers/ Reactors

Ten Delta for bushing at 200C

0.007

IEC – 60137

Capacitance for

Bushing

-5% to +10% Variation

 

Contact Resistance

of Bushing

10 Micro Ohm/Connector

NGC, UK

Recommendation

Ten Delta for

Windings at 200C

0.007

IEEC/C57.12.90.1999

Ten Delta for Windings at 200C

(Power factor)

0.005

Transformer Diagnostic USBR, June 2003

Rate of Rise of Tan

Delta (Bushing & Winding)

0.001 Per year (Max)

 

Magnetizing current

test (Excitation

If the excitation current is less than 50 milli amperes

(mA), the difference between the two higher currents

Transformer Diagnostic

USBR, June 2003


 

current test)

should be less than 10%. If the excitation current more than 50 mA, the difference should be less than 5%. In general, if there is an internal problem, these differences

will be greater.

 

Magnetic Balance Test (Three Phase)

Value of supply voltage (230 V AC) in one phase is equal to sum voltage induced in other two phase.

When supply voltage in middle limb, voltage induced in outer limbs should equal and roughly half of the supply voltage.

 

Winding resistance Transformer and

Reactor (Resistance converted to 750C)

± %5 difference between phases or from Factory tests.

 

Voltage Ratio of Transformer (All Taps)

± %5 difference from Factory tests.

 

Insulation Value (Thumb Rule/ Empirical Formula)

Min insulation values for one minute resistance measurement for transformers may be determined by using the following formuls:

R = CE/ √kVA Where

R = Insulation resistance, in MΩ

C= 1.5 for oil filled transformers at 200C, assuming that the transformer’s insulating oil is dry, acid free, and sludge free.

= 30.0 for un-tanked oil impregnated transformers. E – Voltages rating, in V, of one of the single phase windings (ph – to ph for delta connected and ph – to neutral for wye connected transformers)

kVA = Rated capacity of the winding under test ( If the winding under test is three-phase and the three individual windings are being tested as one, the rated capacity of three-phase winding is used.

 

IR Value of Winding (Min)

Rated Voltage Class of

winding

Min desired IR value at 1

minute at 300C (Mega ohm)

 

11 kV

300

33 kV

400

66 kV & above

500

Polarization index (Ratio of IR values at 10 min to 1 min)

Polarization index

Insulation Condition

 

Less that 1

Dangerous

1.0-1.1

Poor

1.1-1.25

Questionable

1.25- 2.0

Fair

2.0-4.0

Good

Above 4.0

Good

CORE INSULATION

TEST Min (Between CL and CC +G with tank grounded)

1000K Ohms at 2.5/3.5 kV DC for 1 min

 

Transformer Neutral

Resistance Value

Below 1 ohm

 

Turret/ Neutral

Resistance Value

±3%

IS – 2705

Vibration level for

Reactors

200 Microns (Peak to Peak)

60 Microns (Average)

 

Sweep Frequency Response Analysis

Test (20 Hz to 2

In general, changes of +/- 3 dB (or more) in following frequency range may indicate following faults:

Frequency Range

Euro – Double Client Committee Transformer

Diagnostic


 

MHz)

Probable Fault 5Hz to 2 KHz

Shorted turns, open circuit, residual magnetism or core movement

50 Hz to 20 KHz

Bulk movement of windings relative to each other 500 Hz to 2 MHz

Deformation within a winding 25 Hz to 10 MHz

Problems with winding leads and/ or test lead placement.

USBR, June 2003

Moisture measurement of winding (RVM

Measurement)

IEEE Std. 62-1995

 

Insulation condition

% Moisture by dry weight in

paper (Wp)

% Water saturation of oil ( )

CIGRE DOC No. 227.

Life management Technique for Power Transformer Page 119

Dry (at

commissioning)

0.5- 1.0%

<5%

Normal in operation

<2%

 

Wet

2-4%

6-20%

Extremely wet

>4.5%

>30%

Degree of

polymerization (DP)

New insulation

1,000 DP to 1,400 DP

EPRI’s Guidelines for the life Extension of Substations, 2002

Update, Chapter 3,

Table 7

DP Values for Estimating Remaining paper life.

 

60% to 66% life remaining

500 DP

 

30% life remaining

300 DP

 

0 life remaining

200 DP

1.5

CIRCUIT BREAKERS

Dew Point of SF6

Gas

Dew point values as per Annexure – II

 

Dew Point of

operating air

+450C at Atmospheric Pressure

 

(A) CB Operating timing

400 kV

220 kV

132 kV

IEC-62271-100 (2001)

(a) Closing time

(Max)

150 ms

150 ms

150 ms

 

(b) Trip time (Max)

25 ms

35 ms

45 ms

IEC-62271-100

(c) Close/Trip time pole discrepancy at

rated operating pressure

50 ms

3.33 ms

5.0 ms

3.33 ms

5.0 ms

3.33 ms

2001

- Phase to Phase

(Max) close open

2.5 ms

2.5 ms

2.5 ms

IEC-62271-100 (2001)

-Break to Break

(Max) of same phase

35 ms

300 ms

35 ms

300 ms

35 ms

300 ms

 

(d) CO time (min)

±5 ms

±3ms

±5 ms

±3ms

±5 ms

±3ms

With simultaneous

close & trip command.

(e) Trip delay time for DCRM test (CO

operation) Minimum

 

 

(f) Deviation from standard timings as per GTP of manufactures close

open

 

 


 

(B) Travel of operating rod

ABB CGL BHEL

Alstom (Imported)

200 mm

230 mm

130 mm

184 mm

IEC-62271-100 (2001)

(C) PIR time

-  BHEL make

-  CGL make

-  ABB mak

-  NGEF make

-  M&G make

-  TELK make - Alstom make (HVDC)

-ABB make (HVDC)

400 kV

12-16 ms

8-12 ms

8-10 ms

8-12 ms

8-12 ms

8-12 ms

8-12 ms

8-12 ms

Manufactures Recommendations.

(D) PIR operating time prior to opening of main contacts

(ABB, CGL, NGEF

make CBs)

5 ms (Min) at rated pressure

 

(E) PIR and main contacts overlap time (BHEL, M&G, ABB (imported make CBs)

5 ms (Min) at rated pressure

 

(F) Tan delta of

grading capacitors

0.007

Since temperature correction factor for Tan Delta depends on make, type and also again conditions, the correction factors for different types/ makes are different. Hence no standard temperature error factors can be

applied

(G) Rate of rise in Tan dalta

0.001 per year (max)

(H) Capacitance of

grading capacitors

Within ±5% of the rated value

 

(I) Contact Resistance of CB (in

Micro-Ohm)

400 kV                    220 kV                  132 kV 150

100                         100

 

(J) Contact

Resistance of CB terminal connector

10 Micro-Ohm per connector

NGC, UK

Recommendations

(K) Evacuation level

before SF6 gas filling

5mbar (min)

 

(L) N2 leakage rate

from N2 accumulator

3 bar per year (max)

 

(M) IR VALUE

 

 

1. Phase Earth

2. Across open contacts

3. Control cables

1000 M-Ohm (Min) by 5.0/10.0 kV megger 1000 M-Ohm (Min) by 5.0/10.0 kV megger

 

50 M-Ohm (Min) by 0.5 kV megger.

 

(N) PRESSURE SWITCH SETTINGS

- SF6 gas pressure switches

 

 

Within ±0.1 Bar of set value.

 


 

-  Operating air pressure switches

-  Operating oil pressure switches

Within ±0.1 Bar of set value

 

Within ±0.1 Bar of set value

 

(O) BDV of oil used for MOCB

- At the time of filling

-During O&M

 

 

40 kV at 2.5 MM GAP (Min)

20 kV at 2.5 MM GAP (Min)

 

Manufactures Recommendations

1.6

CURRENT TRANSFORMERS

(A) IR Value

-Primary Earth

-Secondary – Earth

-Control Cables

1000 M –OHM (Min)

50 M-OHM (Min)

50 M-OHM (Min)

by 5.0/10.0 kV Megger by 0.5 kV Megger

by 0.5 kV Megger

Tan delta value

0.007

Since temperature correction factor for Tan Delta depends on make, type and also ageing conditions, the correction factors for different types/ makes are different. Hence, no standard temperature error factors can be

applied.

Rate of rise in Tan Delta

0.001 per year (max)

 

(B) Monitoring of Tan delta

·   Upto 0.007 (rise @ 0.001)

·   0.007 to 0.011

·   0.011

-       Yearly monitoring

-       Half yearly monitoring

-       Replace the CT

 

Terminal connector

contact resistance

10 Micro-Ohm per connector

NGC, UK

Recommendations

CT ratio errors

±3% protection cores

±1% metering cores

IS – 2705

- do-

 

Pressure

0.10 kg/cm2

0.20 kg/cm2

0.30 kg/cm2

0.40 kg/cm2

0.50 kg/cm2

Oil level 10 mm

30 mm

50 mm

70 mm

90 mm

 

1.7

CAPACITIVE VOLTAGE TRANSFORMERS

(A) Tan Dalta

0.007

Since temperature correction factor for Tan Delta depends on make, type and also ageing conditions, the correction factors for different types/ makes are different. Hence, no standard temperature error factors can be

applied.

(B) Rate of rise in Tan Delta

0.001 per year (max)

(C) Change in Tan from pre commissioning value

Measurement Value Measurement Frequency

Upto +0.002          - Three yearly

+0.002 to +0.003 - Yearly Above +0.003        - alarming

 


 

(D) Capacitance

Within ±5% of pre commissioning value

 

(E) Contact resistance of

terminal connector.

10 Micro-OHM per connector

NGC, UK

recommendations

(F) Change in capacitance from pre commissioning value

Measurement Value Measurement Frequency

Upto ±2%             - Three yearly

±2% to ±3             - Yearly

Above ±6%           - alarming (needs replacement)

 

 

1000 M-OHM (Min) by 5.0/10.0 kV Megger 50 M-OHM (Min) by 0.5 kV Megger

50 M-OHM (Min) by 0.5 kV Megger

 

(G) Drift in secondary Voltage (to be measurement in 0.2/0.5 class

multimeter)

 

 

 

Condition Frequency

Measurement

 

Upto ±0.5 volts

±0.5 to ±0.8 volts

±0.8 to ±1.2 volts

±1.2 to ±2.0 volts

above +2.0 volts

-0.8 to -4.0 volts less than -4.0 volts

Healthy

To be monitored Close monitoring Close monitoring Alarming

Close monitoring Alarming

Six month 03 monthly monthly

15 days replacement 15 days

replacement

 

(H) EMU tank oil parameters BDV (Min) Moisture content (Max)

Resistivity at 900C Acidity

IFT at 270C

Tan delta at 900C Flash Point

 

IS- 1866

30 kV (GAP 2.5 MM)

35 PPM

 

0.1*1012 OHM-CM

0.5 mg KOH gm (Max)

0.018 N/M (Min)

1.0 Max 1250C (Min)

 

(I) CVT voltage ratio

errors

±5% protection cores

±5% metering cores

IEEE/C93.1.1990

IEC 186

1.8

DISCONNECTING SWITCHES

 

(A)  Contact resistance

(B)  Contact resistance of terminal connector

(C)  IR Value

-  Phase Earth

-  Across Open Contacts

-  Control cables

300 Micro – Ohm (Max)

 

10 Micro-Ohm per connector

 

 

1000 M-Ohm (Min) by 5.0/10.0 kV megger 1000 M-Ohm (Min) by 5.0/10.0 kV megger

 

50 M-Ohm (Min) by 5.0 kV megger

NGC, UK

recommendations

1.9

SURGE ARESTER

 

 

(A) Third Harmonic Resistive Current (THRC)

– for all makes Elpro/ Alstom / Oblum/ CGL

-   For new Las

-   For Las in services

·      Upto 30 Micro – Ohm

·      (Upto 150 Micro Ohm) Normal

·      (150 to 350 Micro-Ohm) – to be tested for insulation test & if value found low

-  to be removed from service.

·      Beyond 350 Micro Ohm (Gapless type)

-  to be removed from service

·      Beyond 350 Micro Ohm (Gapless type)

-  to be removed from service

 

(B) IR Value

1000 Mega-Ohm (Min)

 


1.10

MICELLANEOUS

(A)  Station Earth Resistance

(B)  Thermovision Scanning

-   Temp upto 150C (above ambient)

-   Temp above 15-500C

(above ambient)

-   Temp above 500C (above ambient

 

 

1.0 Ohm (Max)

 

-       Normal

 

 

-       Alert

 

 

-       To be immediately attended.

 

 

 

 

 

IEEE/C37.010.1979

(C) Therminal Connectors

10 Micro-Ohm per connector

NGC, UK

recommendations,

(D)  IR Values

-   All Electrical Motors.

-   Control Cables

-   LT Transformer

-   LT Switchgears

 

50 M-Ohm (Min) by 0.5 kV megger

 

50 M-Ohm (Min) by 0.5 kV megger 100 M-Ohm (Min) by megger

100 M-Ohm (Min) by 0.5 kV megger

 

 

IS 900

1.11

BATTERIES

(A)  Terminal

connector resistance

(B)  Specific Gravity

10 Micro-Ohm ±20%

 

 

1200 ± 5GM/L at 270C

 

ANSI/IEEE/450-1987

1.12

DG SET

(A) Winding IR value

(B)  Stator winding resistance

50 M-Ohm

Within ± 10% of STD value

 

 

 

 

DEW POINT OF SF6 GAS

 

Sl. No.

Make of CB

Dew Point at rated

pressure

Dew point at Atmospheric

Pressure (Limit)

Remarks

1

BHEL

-150C

-360C

At the time of commissioning

-70C

 

During O&M

-50C

 

Critical

2

M&G

 

-390C

At the time of commissioning

 

-320C

During O&M

3

CGL

-150C

-350C

At the time of commissioning

-100C

-310C

During O&M

4

ABB

-150C

-350C

At the time of commissioning

-50C

-260C

During O&M

5

NGEF

-150C

-360C

At the time of commissioning

-70C

-290C

During O&M

-50C

-270C

Critical

6

For all make

-150C

-350C

To be followed for

substations having ambient temperature less than 00C

*

Post a Comment (0)
Previous Post Next Post