Busbar size calculation is crucial in designing electrical distribution systems to ensure the safety and efficiency of power transmission. The busbar serves as a central point for collecting power from incoming circuits and distributing it to outgoing circuits. Calculating the correct size ensures that the busbar can handle the required current without overheating, which could otherwise cause insulation damage, faults, or fire hazards.
Key Factors in Busbar Size Calculation
Current-Carrying Capacity (Ampacity):
- The main factor determining the size of a busbar is its current-carrying capacity, or ampacity, which refers to the maximum current that the busbar can safely carry without exceeding temperature limits.
- Ampacity is influenced by factors such as material type (copper or aluminum), temperature rise, ambient temperature, and installation conditions (e.g., whether the busbar is in open air or an enclosed environment).
Material of the Busbar:
- Copper: Copper has a high conductivity and is often preferred for busbars due to its superior electrical performance. It has a higher current-carrying capacity than aluminum for the same cross-sectional area.
- Aluminum: Aluminum is lighter and less expensive but requires a larger cross-sectional area than copper to carry the same current due to its lower conductivity.
Cross-Sectional Area:
- The cross-sectional area of a busbar is determined based on the ampacity requirement. The cross-sectional area (A) is given by:
where:
- = Current in amperes (A)
- = Current density (A/mm²)
- The current density is typically chosen between 1.2 to 2.5 A/mm² for copper and 0.8 to 1.6 A/mm² for aluminum, depending on factors like cooling and insulation.
- The cross-sectional area of a busbar is determined based on the ampacity requirement. The cross-sectional area (A) is given by:
where:
Voltage Drop:
- For longer busbar lengths, it is important to consider the voltage drop along the busbar. The voltage drop () can be calculated using:
where:
- = Resistivity of the material (Ω·mm²/m)
- = Length of the busbar (m)
- = Cross-sectional area (mm²)
- Ensuring a minimal voltage drop is important for maintaining efficient power distribution across the busbar.
- For longer busbar lengths, it is important to consider the voltage drop along the busbar. The voltage drop () can be calculated using:
where:
Short Circuit Capacity:
- Busbars must withstand the thermal and mechanical stresses during short-circuit conditions. This depends on the material's thermal capacity and short-circuit current duration.
- The formula for short-circuit current withstand capacity is:
- where:
- = Short-circuit current (A)
- = Constant dependent on material and temperature (e.g., for copper is about 143 for 1 second)
- = Cross-sectional area (mm²)
- = Time in seconds
- where:
Determine the Current Requirement:
- Suppose the required current is 1000 A.
Select Material:
- Let’s choose copper as the busbar material.
Determine the Current Density:
- Assume a current density of 1.6 A/mm² for safe operation.
Calculate the Cross-Sectional Area:
- Using the formula :
- This indicates that a cross-sectional area of at least 625 mm² is required for the busbar.
Verify for Voltage Drop:
- Let’s assume a busbar length of 10 m and a resistivity of 0.0175 Ω·mm²/m for copper:
- If this voltage drop is within acceptable limits (often less than 3% of the operating voltage), the selected area is suitable.
Check Short-Circuit Capacity:
- For a 1-second duration and copper with :
- This indicates that the busbar can withstand a short-circuit current of up to 89,375 A for 1 second.
- Busbar Shape: Typically, busbars have a rectangular cross-section to maximize surface area for heat dissipation. Thinner, wider bars can provide better cooling.
- Insulation and Spacing: For high-current applications, proper insulation and spacing between busbars are essential to avoid arcing and ensure safety.
- Derating Factors: Adjust the ampacity if the busbar is installed in conditions that affect heat dissipation, like enclosed cabinets or high ambient temperatures.
Step-by-Step Calculation Example
Here's a step-by-step approach to calculate a busbar's size:
Practical Considerations
By taking into account these calculations and considerations, the appropriate size of the busbar can be determined, ensuring that it operates safely and efficiently within the designed electrical system.
So, the secondary current is 2225 A. This value will determine the size of the busbar since it carries a much higher current than the primary side.
Step 2: Choose Busbar Material
Busbars are typically made of copper or aluminum, and their size depends on the material used because of differences in conductivity.
- Copper has a higher current-carrying capacity compared to aluminum.
- Aluminum is lighter and cheaper but requires a larger cross-section for the same current capacity.
Step 3: Determine Current Density
The current density varies based on the material and installation conditions:
- Copper: 1.2 to 1.6 A/mm² for enclosed busbars or higher if properly ventilated.
- Aluminum: 0.8 to 1.0 A/mm² for enclosed busbars.
For this calculation, we'll assume 1.25 A/mm² for copper as a reference.
Step 4: Calculate the Cross-sectional Area
Step 6: Consider Design Factors
When selecting the busbar size, consider factors like:
- Ambient temperature and derating factors.
- Voltage drop and short-circuit current rating.
- Busbar enclosure and cooling methods.
A safety factor is also often applied to ensure the busbar size is adequate under varying conditions.
Summary
For a 1600 kVA, 11kV/415V transformer with 2225 A on the secondary side:
- Copper Busbar: Approx. 100 mm x 18 mm or 100 mm x 9 mm (double arrangement).
- Aluminum Busbar: Approx. 100 mm x 28 mm or 100 mm x 14 mm (double arrangement).
These dimensions are estimates, and final selections should account for specific site conditions and standards.
Click here