EQUIPMENT IN DISTRIBUTION SUB-STATION

Electrical General Services Sub-station is a distribution sub-station from which electric supply is distributed to the different users. In a substation there are numbers of incoming and outgoing circuits each having its isolator, circuit breaker, transformers etc. connected to bus-bar system. These equipment are mostly static type. Safety and protection of equipment as well as working personnel is also a considerable factor. Lightening arresters, earthing of equipment and fencing is done for this purpose. Maintenance of a sub-station is essential to ensure un-interrupted electric supply to the using points which involves vigilance, care and well-defined scheme of procedures. Such scheme indicates the authority and responsibility of persons at various levels. It consists of many of periodic schedule maintenance, regular inspections, testing and rectification of defects. 

Upkeepment of records of each inspection is essential. If any replacement is carried out or adjustment of certain setting is done then these must be entered in a logbook. A rigid system of maintenance of each equipment will ensures long life, trouble free service and reduction in unnecessary interruptions. All work on major electrical installations must be carried out under permit to work system.

The “permit to work” is to be issued through permit card only by an authorized person. As the name suggests it authorizes the maintenance supervisor and his team to carry out work. Furthermore, this card will indicate unambiguously the points at which it is safe to work, the time interval when it is to be done, steps to be taken to ensure safety such as earthing, display of danger notices etc. at the nearest live point. It should have the signature of the authorized person. After the work is completed the permit card should be cancelled and it should be taken back. Danger notices should be put up or removed by the responsible supervisor who will take the charge of keys equipment, rooms, etc


1.1             EQUIPMENT IN DISTRIBUTION SUB-STATION

 

The following equipment are installed in Electrical General Services Sub-station:

1.              Distribution Transformer

2.              Circuit breaker

3.              Lightning Arrester

4.              Air Break (AB) switches/ Isolator

5.              Insulator

6.              Bus-bar

7.              Capacitor Bank

8.              Earthing

9.              Fencing

10.          Distribution panel board

 

1.1.1         Distribution Transformer

 

The distribution transformer is a main and largest equipment of Electrical General Service Sub-station. It is basically a static electrical device which steps down the primary voltage of 33kV or 11 kV to secondary distribution voltage of 415-440 volts between phases and 215 volts between phase and neutral through delta-star windings by electromagnetic induction without change in frequency.

 

Transformer consists of the following parts and components.

 

·         Primary winding                                 Secondary winding

·         Transformer tank                                Conservator

·         Cooling tubes                                      Breather

·         Buchholz Relay                                   Explosion vent

·         Tap changer                                        Oil inlet valve

·         Oil outlet valve                                   Oil level indicator

·         L.T. terminals                                      H.T. terminals

·         Temperature gauge


F     Working of Important Components

·                     Conservator Equipped with transformer of rating 500 kVA & above


It is a drum containing transformer oil and mounted at the top of the transformer and connected to the main tank by a pipe. As the volume of oil of transformer tank expands and contracts
according to heat produced, this expansion and contraction of oil causes the level of the oil in conservator to rise and fall. The aim of conservator is to
  1. maintain the oil level in tank
  2. provide space for the expanded oil.


·                     Breather
It is attached to conservator tank and contains silica gel, which prevents the moist air from entering into the tank during contraction of oil. When oil is hot there is expansion and gas passes to atmosphere through it. When oil is cooled, it contracts and the air enters in it. It prevents transformer oil from moisture contamination.

•Buchholz Relay

It is protective relay of transformer. This device signals the fault as soon as it occurs and cuts the transformer out of the circuit immediately. This is gas operated protective relay. It is installed in between the pipe connecting the tank and the conservator. This relay works on the formation of excessive oil vapors or gas inside the transformer tank due to internal fault of transformer. It consists of two operating floats A and B. These are operated by two mercury switches separately provided for each float. The float A is for bell alarm and float B is for operating the tripping circuit.

 


Whenever there is a minor fault or low level of oil, the bell alarm operated by float ‘A’ and whenever there is severe fault in the transformer, float ‘B’ operated due to excessive gases. It trips the circuit breaker and transformer is put out of circuit.

·                    
Explosion Vent



A major fault inside the transformer causes instantaneous vaporization of oil, leading to extremely rapid buildup of gaseous pressure. If this pressure is not released with in few milliseconds, the transformer tank can rupture, spilling oil over a wide area. An explosion vent provides instantaneous releasing of such dangerous pressure and protects the transformer. 

Oil level Indicator


 It indicates level of transformer oil at the conservator of the transformer. It has markings on transparent sheet for maximum & minimum levels.

 Inlet Valve

It provides passage to pour the transformer oil in the tank during purification or in case of shortage found in the tank.

Outlet Valve

It provides passage to drain the oil during overhauling or as and when required oil sample for testing.

Cooling Tubes

These tubes provide better and effective cooling of transformer oil by increasing the surface area of tank to the atmosphere.

Tape changer

The tape changer is used to regulate the out- put voltage manually according to line voltage. The tapes of transformer can be changed by the tape changer manually. It is provided on HV side so that the voltage on LV side feeding to the load can be maintained. Normally tap selection range is ± 15 % in steps of 2.5 %


  

   Circuit Breaker

 The circuit breaker is an equipment which automatically cut off power supply of the system when any fault or short circuit occurs in the system. It detect and isolate faults within a fraction of a second thereby minimizing the damage at the point where the fault has occurred. The circuit breakers are specially designed to interrupt the very high fault currents, which may be ten or more times the normal operating currents.

 There are many types of circuit breakers, e.g. Oil, minimum oil, Air blast, Vacuum, SF6, etc. being used at sub-stations. This list is generally in order of their development and increasing fault rupturing capacity, reliability and maintainability. In distribution sub- station, generally oil circuit breakers and air circuit breakers are used.

 Lightning Arrester

Lightning arrester is a most important protective device of distribution sub-station to protect valuable equipment as well as working personnel. It arrests and discharges over voltage to earth during lightning strokes. These are installed between line and earth near equipment.

Representative values of a lightning stroke:

 Voltage - 2 x 108 volts.-    Current - 2 x 104 Amps-    Duration - 10-5 seconds.-    Power - 8 x 105 kW



Air Break (AB) Switch/ Isolator


 Air break switches are used to isolate equipment for maintenance and also for transfer of load from one bus to another. Lay-out of sub-station depends upon type of Air break switches. These switches are of two types viz. vertical break type or horizontal break type. Horizontal break type normally occupies more space than the vertical break type.


  Insulator

The main function of an insulator is to insulate live conductor or equipment at different voltages with reference to the ground structures as well as provide mechanical support. Provision of adequate insulation in a substation is of primary importance from the point of view of reliability of supply and safety of personnel.

  Bus Bar Arrangement

The bus bar is a conductor used to connect two and more equipment located side-by- side when the currents are very high. These are usually rectangular, sometimes tubular, bare copper bars supported on insulators. The outdoor bus-bars are either of the rigid type or of the strain type. In the rigid type, pipes are used for making connections among the various equipment. The strain type bus-bars are an overhead system of wires strung between two supporting structures and supported strain type insulators. Since the bus bars are rigid, the clearances remain constant.

Capacitor Bank

It is a series parallel combination of capacitors required to improve power factor of the system. They act as reactive power generators, and provide the needed reactive power to accomplish active power of circuit. This reduces the amount of reactive power, and thus total power (kVA) or the demand. The bank should be provided as near as possible to load.

 

 Earthing


Provision of an effective, durable and a dependable earthing in a substation and switching stations is very important for the safety of operating personnel as well as electrical devices. The voltage levels do not rise above tolerable thresholds and that the earth connection is rugged to dissipate the fault to the earth. Earthing has a very low resistance and connects the electrical equipment to the general mass of the earth. Earthing of various equipment in sub-station is described in chapter 4, para 4.7.

Fencing Arrangement

Fencing is provided at outdoor sub-station yard for restricting entry of unauthorized person and livestock. It must be earthed/ grounded separately. Height of fencing normally should not be less than 1.8 metres. Fencing should be painted once in a year by suitable paint.

Distribution Panel Board

Distribution panel board consists of MCCBs, control equipment, meters and relays are housed in the control room. The panel frame shall be connected to the earth grid by an earthing conductor. A rubber mat of prescribed size and quality shall lay in front of panel.


*

Post a Comment (0)
Previous Post Next Post